FG17 Cable 1X6mmq 450/750V Brown 100 Meters
Cable FG17 1X6mmq 450/750V Brown for low voltage, fire reaction in accordance with CPR Regulation 305/2011/EU.
- Approximate conductor diameter 3.0mm
- Average insulation thickness 0.8mm
- Max. outer diameter 5.3mm
Sold in 100 Meter skein.
- Baldassari cavi
- Icel
- La Triveneta
- Prysmian
FG17 Cable 1X6mmq 450/750V Brown 100 Meters
FG17 Cable 1X6mmq 450/750V Brown 100 Meters
Tax included
FG17 Cable 1X6mmq 450/750V Brown 100 Meters
Features:
- Conductor: red copper, flexible formation, class 5
- Insulation: cross-linked elastomeric LS0H, G17 quality
- Rated voltage Uo/U: 450/750 V
- Maximum operating temperature: 90°C
- Minimum operating temperature: -30°C (in the absence of mechanical stress)
- Maximum short-circuit temperature: 250°C
- Good flowability in pipes, good abrasion resistance, excellent strippability
- Minimum laying temperature: -15°C
- Recommended minimum bending radius: 4 times the cable diameter
- Maximum recommended tensile stress: 50 N/mm2 of copper cross section
- Approximate conductor diameter 3.0mm
- Average insulation thickness 0.8mm
- Maximum outer diameter 5.3mm
- Max electrical resistance at 20°C /km 3.30
Suitable in environments where safeguarding people is essential: schools, offices, theaters, subways, hospitals, places of worship, shopping malls, and places of public performance and entertainment. For installation within exposed or recessed piping or similar closed systems. For fixed and protected installation within lighting fixtures or switching and control equipment. When installation is protected within interrupting or control equipment this cable is permitted for voltages up to 1000 V a.c. or 750 V d.c. in relation to earth. Suitable for bundled installations in environments with higher risk in case of fire. Not suitable for outdoor installation
Reference Construction Products Regulation 305/2011 EU and Standard EN 50575: Given the properties of limiting the development of fire and noxious fumes, the cable is suitable for power supply in buildings and other civil engineering works
Reaction to fire:
- EN 50575:2014+A1:2016 standard
- Class Cca-s1b, d1, a1
- Classification: (IEC UNEL 35016) EN 13501-6
- Heat and smoke emission during flame development.
- Vertical flame propagation: EN 60332-1-2
- Corrosive and halogenated gases: EN 60754-2
- Smoke density (transmittance): EN 61034-2
- Notified Body: 0051 - IMQ
- C E 2019.