Schneider TeSys LC1D Contactor 3P 9A AC3 24V AC LC1D09BD


SNR LC1D09BD 3389110353075

Schneider TeSys LC1D contactor with the following characteristics:

  • Number of poles: 3
  • Rated operating voltage
  • Ue: <= 690 V "AC" 25...400 Hz Power circuit - <= 300 V DC Power circuit
  • Rated use current
  • Ie: 9 A 60 °C) "AC" AC-3 for Power circuit at <= 440 V - 25 A 60 °C) "AC" AC-1 for Power circuit at <= 440 V - 9 A 60 °C) "AC" AC-3e for Power circuit at <= 440 V
  • Contact pole composition: 3 NO
  • Contact compatibility: M4
  • Auxiliary contact composition: 1 NO + 1 NC
  • Rated impulse withstand voltage: 6 kV in accordance with IEC 60947
Do you have questions about this product or did you not find what you were looking for? Ask us!

Schneider TeSys LC1D Contactor 3P 9A AC3 24V AC LC1D09BD

€74.75
€74.75

Schneider TeSys LC1D Contactor 3P 9A AC3 24V AC LC1D09BD

€74.75
Tax included

Schneider TeSys LC1D Contactor 3P 9A AC3 24V AC LC1D09BD

€74.75

Buy it within and receive it from Thursday, 12 December
Two-year warranty
Easy return within 14 days

LC1D09BD is a compact 3-pole TeSys D contactor from Schneider Electric for motor applications. Rated 9 A AC-3 4 kW at 400 V, it includes a 24 V DC coil and 1NA+1NC auxiliary contacts. Can be used in safety applications due to the certified NC mirror contact. Compact, DIN-rail-mounted, it ensures high reliability and durability. Available worldwide, it is certified to various standards (IEC, UL, CSA, CCC, EAC, for use in marine environments) and is Green Premium (RoHS/REACH) compliant.


Advantages:

  • Compact product, 45 mm wide, for DIN rail and panel mounting.
  • Separation between power and control circuits, easy front access to coil and auxiliary contact connections.
  • Equipped with a 24 V DC coil for easy integration into all control systems.
  • Features 2 built-in 1NA+1NC auxiliary contacts.
  • High electrical durability, guaranteed for 2 million cycles at 9 A AC-3 440 V

Motor power:

  • 2.2 kW at 220...230 V "AC" "50/60 Hz" (AC-3)
  • 4 kW at 380...400 V "AC" "50/60 Hz" (AC-3)
  • 4 kW at 415...440 V "AC" "50/60 Hz" (AC-3)
  • 5.5 kW at 500 V "AC" "50/60 Hz" (AC-3)
  • 5.5 kW at 660...690 V "AC" "50/60 Hz" (AC-3)
  • 2.2 kW at 400 V "AC" "50/60 Hz" (AC-4)
  • 2.2 kW at 220...230 V "AC" "50/60 Hz" (AC-3e)
  • 4 kW at 380...400 V "AC" "50/60 Hz" (AC-3e)
  • 4 kW at 415...440 V "AC" "50/60 Hz" (AC-3e)
  • 5.5 kW at 500 V "AC" "50/60 Hz" (AC-3e)
  • 5.5 kW at 660...690 V "AC" "50/60 Hz" (AC-3e)

Motor power in hp:

  • 1 hp at 230/240 V for 1 phase motors" AC" "50/60 Hz"
  • 2 hp at 200/208 V for 3 phase motors" AC""50/60 Hz"
  • 2 hp at 230/240 V for 3 phase motors" AC" "50/60 Hz"
  • 5 hp at 460/480 V for 3 phase motors" AC" "50/60 Hz"
  • 7.5 hp at 575/600 V for 3 phase motors" AC" "50/60 Hz"
  • 0.33 hp at 115 V for 1 phase motors "AC" "50/60 Hz"

Rated insulation voltage:

  • 690 V complying with IEC 60947-4-1 Power circuit
  • 600 V CSA certified Power circuit
  • 600 V UL certified Power circuit
  • 690 V complying with IEC 60947-1 signaling circuit
  • 600 V CSA certified signaling circuit
  • 600 V UL certified signaling circuit

Characteristics:

  • Conventional thermal current in open air: 25 A at <60 °C for Power circuit - 10 A at <60 °C for signaling circuit
  • Rated closing power Irms: 250 A at 440 V per IEC 60947-compliant Power circuit - 140 A "AC" per IEC 60947-5-1-compliant signaling circuit - 250 A DC per IEC 60947-5-1-compliant signaling circuit
  • Rated breaking capacity: 250 A at 440 V per IEC 60947-compliant power circuit
  • Associated fuse rating: 10 A gG for signaling circuit complying with IEC 60947-5-1 - 25 A gG at <= 690 V Type 1 coordination for Power circuit - 20 A gG at <= 690 V Type 2 coordination for Power circuit
  • Time constant: 28 ms
  • Minimum switching current: 5 mA per signaling circuit
  • Minimum switching voltage: 17 V per signaling circuit
  • No-overlap time: 1.5 ms upon deactivation between NC and NO contact - 1.5 ms upon activation between NC and NO contact
  • Inrush power in W: 5.4 W 20 °C)
  • Holding power consumption W: 5.4 W at 20 °C
  • Insulation resistance: > 10 MOhm per signaling circuit
  • Dimensions: height 77 mm - width 45 mm - depth 95 mm
  • Weight: 480 grams

Data sheet

Type:
Contactors
Voltage:
24V
Poles:
3P
Degree of protection:
IP20