Unit power factor correction Ducati 50-M 17,5 KVAR 415V 7 steps 415040030
Unit power factor correction automatic Ducati 17,5 KVAR 415V 7 steps Power battery 2.5 + 5 + 10 (kVAr), In 23A, In sec. 40A, Dimensions: Wxdxh 400x270x400mm.
Unit power factor correction Ducati 50-M 17,5 KVAR 415V 7 steps 415040030
Unit power factor correction Ducati 50-M 17,5 KVAR 415V 7 steps 415040030
Tax included
Unit power factor correction Ducati 50-M 17,5 KVAR 415V 7 steps 415040030
Capacitors single-phase series MONO Long Life 4In metallized polypropylene, which are characterized by high ability to be able to work in systems with high harmonic currents. Rated voltage to 415V
Avr micro processor series START&GO. Immediate installation without any setup required, and simple and intuitive interface. Operation with cogeneration systems (e.g. photovoltaic)
Carpentry steel sheet painted with epoxy powders RAL 7035
Switch omni-polar with door interlock and the current nominal dimensioned 1.45 In according to CEI EN
Contactor suitable for capacitive loads with devices limiting the inrush current of power supply 230 V, 50 - 60 Hz
Features:
- Mains voltage (use) 400V
- Rated frequency 50 Hz
- Insulation voltage 690 V
- Natural Ventilation
- Installation For interior wall
- Degree of protection IP30
- Continuous Service
- Class temperature framework -5 +40 °C
- Power supply 3P + PE + N
- Cable entry From the top
- Internal links FS17
- Discharge devices Provided on each battery
- Fuses NH-00 GL
- Short-circuit current of 50 kA (influenced by upstream protection).
Data sheet
- Type:
- Power factor correction unit