Beta Cavi fire resistant cable 2x2.5 sq. mm LSZH sheath Red 200m


BTV FRHRR2250SF200 9000003882703

Fire-resistant shielded cable for fixed automatic fire detection and fire alarm signaling systems Beta Cavi FTE29OHM16 with the following characteristics:

 

  • PH circuit integrity: PH120
  • Formation: 2x2.5 sq. mm
  • Pair capacitance: 79 pF/m
  • Resistance: 7.9 DC /KM
  • Outer diameter: 9.40 mm
  • LSZH Sheath Red
  • Fire Reaction Classification: Cca s1b, d1, a1
  • Installation: Indoor and Outdoor

     

The selling price is intended per meter.

 

Minimum saleable quantity: hank of 200 meters.

Do you have questions about this product or did you not find what you were looking for? Ask us!

Beta Cavi fire resistant cable 2x2.5 sq. mm LSZH sheath Red 200m

€1.88
€1.88

Beta Cavi fire resistant cable 2x2.5 sq. mm LSZH sheath Red 200m

The minimum purchase order quantity for the product is 200.

€1.88
Tax included

Beta Cavi fire resistant cable 2x2.5 sq. mm LSZH sheath Red 200m

€1.88

The minimum purchase order quantity for the product is 200.

Buy it within and receive it from Monday, 11 November
Two-year warranty
Easy return within 14 days

As a result of the latest regulatory developments, the cables used in a fire alarm detection and warning system will necessarily have to comply with the new product standard CEI 20-105V2, test methodology CEI EN 50200 and EU regulation 305:2011 according to Euroclass Cca s1b d1 a1.

 

These characteristics guarantee not only the maintenance of the functionality of the installation under fire conditions, but also the safety for the people present according to the new indications introduced by the CPR regulation.

 

A cable complying with the CEI EN 50200 test methodology, ensures the functionality of the loop during the test for a given period of time (a requirement of uni 9795 PH30) but, as a test method, does not provide indications regarding the construction characteristics i.e. the electrical, transmission and mechanical parameters.

 

The fire loop is a BUS-type connection on which runs a digital protocol for communication between apparatuses, therefore, if the real need of the manufacturers of apparatuses for fire detection systems is to connect the system with cables with specific electrical performance in addition to ensuring fire resistance for a given period of time, it is the responsibility of the individual manufacturers to indicate, in addition to fire resistance, the requirements necessary for the proper functioning of the system such as two-point shielding, capacitance, inductance, etc. in order to avoid malfunctions.

 

Characteristics:

  • CPR classification Cca s1b, d1, a1
  • Use with apparatus having operating voltages not exceeding 100 VAC
  • Connection between: control panel and detection points, electric locks, natural smoke and heat evacuators, electromagnets for fire door release
  • Cable for CAT I systems
  • Rated operating voltage Uo/U= 100/100V
  • Rated insulation voltage Uo= 400V
  • Suitable for laying in coexistence with cables for category I systems (e.g., 230V, 400V)
  • Outer sheathing made of Duraflam LSZH red
  • Inner insulation color: 2 conductors red and black

Data sheet

Colour:
Red
Diameter:
9,4mm
Type:
Fire-resistant Cables
Cross-Section:
2.5 mmq
With yellow/green:
No
Number of cables:
2