HT Italia CEI 64-8 safety testing instrument with multimeter functions TRMS M75L
HT Italia instrument for IEC 64-8 safety verification with TRMS multimeter functions.
Accessories included:
- Carrying bag for medium/small instruments and accessories
- Cable with green banana and black shuko plug (HA002075)
- Set of black/green color test leads and alligator clips (HA000158)
- Quick Start Guide and Manual
- Certificate of Calibration
![](https://www.elettronew.com/45980-large_default/ht-italia-cei-64-8-safety-testing-instrument-with-multimeter-functions-trms-m75l.jpg)
HT Italia CEI 64-8 safety testing instrument with multimeter functions TRMS M75L
Tax included
![klarna](/../img/logo-klarna-list.png)
M75L performs the measurement of the Global Earth Resistance, the measurement of the tripping time of AC residual current devices, the measurement of Insulation and Continuity of earth and equipotential conductors in accordance with the regulations in force in civil electrical installations.
To make it versatile and fully usable at any level of end user, the instrument has been inserted in the innovative AUTO function: choosing this function and setting only the value of the current of the RCD, M75L connected to a power outlet, performs in sequence global earth resistance test, test on RCD, Insulation test. At the end of the test all the results will be shown with an indication of whether or not the standard requirements are met with a simple OK or NOT OK symbol. M75L provides several additional functions such as 1-terminal phase cyclic sense measurement, leakage current measurement with optional clamp transducer and a powerful multimeter function for voltage and current measurement in true TRMS RMS value.
Features:
- HT Series Italy
- Power supply: 4 batteries 1.5V type LR6-AA-AM3-MN 1500 (mini-stilo)
- Conversion: AC 16 Bit, TRMS (True Effective Value)
- Sampling Rate: 64 samples / period
- Dimensions (W x L x H): 240 x 100 x 45mm
- Weight: about 630 grams
- Temperature of reference: 23°C + 5°C
- Temperature of use: 0° ÷ 40°C
- Allowable relative humidity: < 70%HR
- Temperature of warehouse: -10 ÷ 60°C
- Storage Humidity: < 70%HR
- Continuity test with 200mA: CEI 64-8 612.2 / IEC/EN61557-4
- Resistance of insulation: CEI 64-8 612.3 / IEC/EN61557-2
- Global Earth Resistance: CEI 64-8 612.6.2 / IEC/EN61557-3
- Residual current circuit breaker testing: CEI 64-8 612.9 and app.D / IEC/EN61557-6
- Cyclic direction of phases: IEC/EN61557-7
- Safety measuring instruments: IEC/EN61010-1 + A2(1997)
- Product standards: IEC/EN61557-1, 2, 3, 4, 6, 7
- Insulation: double insulation
- Pollution degree: 2
- Max usage altitude: 2000m
- Category of overvoltage: CAT III 550V AC (Phase - Earth) - CAT III 550V AC (Phase - Phase)
Display:
- Features: Dual LCD, 4 digits, maximum reading 9999
- Display refresh rate: 2 times/sec
- Visible area: 73 x 73 mm
Data sheet
- Type:
- Multimeters