Ime Multifunctional Meter with active and reactive energy meter MFD4421
IMS MFD4421
8032826046957
Ime multifunctional Meter with active and reactive energy meter with the following features:
- Series: Nemo D4-Le, MFD4
- Auxiliary voltage: 80-265Vac - 100-300Vdc
- Current In: 1-5 Amps
- 4 Modules
- Degree of protection: IP20
- Accuracy class: 0.5/1
- Input: 80-500Vac (3-PH) 50-290Vac (1-PH)
- Output: pulse / pulse + RS485 Modbus
- System type: three-phase / three-phase + single-phase / single-phase
- Insertion: TA /CT
Ime Multifunctional Meter with active and reactive energy meter MFD4421
€226.81
€226.81
Ime Multifunctional Meter with active and reactive energy meter MFD4421
€226.81
Tax included
Tax included
Items Available: 29
Ime Multifunctional Meter with active and reactive energy meter MFD4421
€226.81
Buy it within and receive it from Monday, 11 November
Display:
- Display type: liquid crystal backlit
- Backlight selectable: 0 35 70 100%
- Reading points: 10000 4 digits (digit height 12mm)
- Engineering unit: automatic display according to set TA and TV ratios
- Resolution: automatic
- Decimal point: automatic
- Display update: 1 reading/s
- Energy counting: 8 digits
Input:
- Three-phase rated voltage Un: 400-100V (phase-phase)
- Three-phase voltage: 80 to 500V (phase-phase)
- Single-phase voltage: 50 to 290V
- Rated current in: 5A 1A
- Instantaneous overload: 20 In/0.5s
- Rated frequency fn: 50Hz 400Hz (automatic selection) allowable variation: 45...65Hz (fn 50Hz) 360...440Hz (fn 400Hz)
- Measurement type: true rms value
- Harmonic content: up to 50a harmonic (45...65Hz)
- Current crest factor: 2
- Start-up time (energy counting): < 5s
- Voltage self-consumption: 0.2VA (phase-neutral at rated voltage)
- Current self-consumption: 1VA (per phase at maximum current 6A)
Digital inputs:
- 2 active digital inputs, with different usage in selected counting mode
- Synchronous: active and/or reactive partial energy counting activation
- Asynchronous: unused digital inputs
- Tariff: switching tariff 1 / 2 / 3 / 4
- Pulse counting: pulse counting input 1 and 2 3 input terminals with common point (terminals 23-24-25)
- Maximum input voltage: 27V
- Maximum input pulse rate: 15Hz
Features:
- Size: active power
- Calculation: fixed average, over the selected period
- Integration time: 5/8/10/15/20/30/60 min
- Counting hours and minutes
- Counting start: selectable, voltage presence opp. power
- Voltage: phase voltage > 20V
- Power: three-phase active rated power programmable value: 0.1...50%Pn
- Pn = Rated three-phase active power = Rated three-phase voltage Un x Current In x 3
- Un = 400V
- In = 1A or 5A
- Pn = 400V x 5A x ?3 = 3464W opp. 400V x 1A x ?3 = 692.8W
Data sheet
- Type:
- Electricity meters
- Amps:
- 5A