Single core medium voltage cable RG26H1M16 1x95 sq. mm 12/20 kV
Single-core medium voltage RG26H1M16 rubber insulated 1x95 sq mm 12/20 kV cable with the following characteristics:
- Outer diameter: 28.8 mm
- Conductor diameter: 11.4 mm
- Insulation thickness: 4 mm
- Sheath thickness: 1.9 mm
Suitable for transporting energy between transformer substations and large utilities; particularly suitable in places with fire hazards, in rooms where equipment, switchboards and instrumentation are concentrated where their protection is essential. For laying in air, pipe or duct.
The selling price is per metre.
- Baldassari cavi
- Icel
- La Triveneta
- Prysmian
Single core medium voltage cable RG26H1M16 1x95 sq. mm 12/20 kV
Single core medium voltage cable RG26H1M16 1x95 sq. mm 12/20 kV
Tax included
Single core medium voltage cable RG26H1M16 1x95 sq. mm 12/20 kV
Single-core HEPR rubber-insulated cables of G26 quality, reduced thickness, with a maximum operating temperature of 105°C. A high operating temperature allows them to be used with about 10% overload in continuous operation and/or higher margins in critical situations than conventional cables.
Appropriate protection is required in case of UV exposure. Permitted for underground laying, in accordance with Article 4.3.11 of IEC 11-17. The cable is suitable for power supply in buildings and other civil engineering works.
Characteristics:
- Conductor: red copper, compact rigid formation, class 2
- Semiconductor layer: extruded
- Insulation (reduced thickness): rubber, lead-free G26 quality (HD 620 DIH 2)
- Semiconductor layer: extruded, cold peelable
- Screen: red copper wires, with copper ribbon in counter coil
- Sheath: thermoplastic LS0H, M16 quality
- Color: red
- Rated operating voltage: 12/20 kV
- Maximum operating voltage: 24 kV
- Maximum operating temperature: 105°C
- Minimum operating temperature: -15°C (in the absence of mechanical stress)
- Maximum short circuit temperature: 300°C
- Minimum laying temperature: 0°C
- Recommended minimum bending radius: 14 times the cable diameter
- Maximum recommended tensile stress: 60 N/mm2 of copper cross section
Data sheet
- Cross-Section:
- 95mmq
- Number of cables:
- 1