Notifier Analog Fire detection Control Panel 4 Loop Clip AM6000CL
Notifier microprocessor-based fire detection control panel for individually addressed analog devices, equipped with 4 loops expandable up to 8. Each loop allows connection of 99 detectors and 99 input/output modules:
- 4 total access levels in accordance with EN 54 standards
- Programmable scripts: point: 32 characters; zones: 32 characters
- 150 Zones / 400 Logical Groups for control panels up to 4 lines
- CBE (Control-by event) control equations for activations with logical operators (AND, OR, DEL , etc.)
- Historical archive from 32000 events resident in non-volatile memory, depending on system size
- Real-time clock
- Auto-programming lines with automatic device recognition
- Decision algorithms for alarm, pre-alarm and fault criteria
- Automatic Day/Night sensitivity switching
- Signaling of need for sensor cleaning
- Programmable alarm threshold for sensors
- Walk-Test function for zones
Notifier Analog Fire detection Control Panel 4 Loop Clip AM6000CL
Notifier Analog Fire detection Control Panel 4 Loop Clip AM6000CL
Tax included
Notifier Analog Fire detection Control Panel 4 Loop Clip AM6000CL
Frequently bought together
The AM6000CL control panel is a multi-microprocessor Fire Detection system suitable for plant configurations of a wide range of sizes. The system offers integrated fire detection solutions for many applications, including hotels, commercial offices and schools. The control panel has a basic of four loops expandable to a maximum of eight loops with the addition of LIB-AMCL expansion boards each loop handles 99 detectors and 99 input/output modules. Programming of the central unit is done via PC programming tool (PK-AMCL). The control panel is certified in accordance with the reference standards UNI EN 54-2, UNI EN 54-4, and system certification EN 54-13, guaranteeing a compliant solution as indicated by the Unified Code.
Strengths:
- The control unit is expandable with up to 2 boards of 2 loops (LIB-AMCL) and is equipped with a 7" Touch Display with color graphics (800 x 480 with backlighting) and 256 colors, programmable lettering options of 32 characters per point and 32 characters per zone
- Allows configuration of 400 logical groups programmable by operator iAND, OR, DEL, XGRP, etc. and 150 zones
- Historical archive of 32000 events in non-volatile memory
- Configurable from keypad or PK-AMCL software
- Ability to manage the control panel using supervision software via ETH port and through connection with the cloud (CLSS) with the addition of the E-SIB protocols enable card
- Also has an additional serial output for connecting remote displays (AM-LCD)
- Certified in accordance with EN 54-2 , EN 54-4 and System Certification EN 54-13
User Interface:
- The ergonomic color LCD Touch user interface is designed so that every operation is easy and intuitive. The control panel has a 7 (800 x 480 with backlight), 256-color TFT touch display for entry of control panel programming data and interaction with operators. All functions are available with access to the 4 password levels as defined by EN 54-2 standards. Through dedicated buttons on the touch screen, there is simplified access to the following functions: Evacuation, Delay Reset, Buzzer Silence, Siren Silence/Reset, Event Reset.
Detection Lines:
- The control panel has 4 to 8 detection lines based on Notifier's proven Loop technology for connecting devices with rotary-switch addressing being the hallmark of Notifier's analog addressed devices
Zones:
- They serve as a basic indication to identify the location of an event, as outlined in EN 54-2. In the maximum configuration of 8 lines the central unit makes 150 Zones available, Up to 32 points can be associated with each zone
Remote displays:
- Up to 32 remote displays with color Touch model AM-LCD can be connected to each central unit via an opto-isolated RS.485 two-wire serial line. Up to 16 of these terminals can be configured to partially display the events of up to 64 zones (typically used as the floor or sector displays in Hotels and Hospitals) while 16 repeat all the events of the entire system.
Connectivity: A hardware key (E-SIB) enables communication to monitoring and supervisory systems, so you can manage your system from a local network location using Notifier supervisory systems or with Honeywell CLSS - Connected Live Safety Services, a cloud platform that monitors the fire detection system in all aspects; from maintenance to checking the status of each individual system component. Also by installing the E-SIB enabling key in each control panel, secure communication via Ethernet with WIN-FIRE Supervision software is possible.
PK-AMCL:
- Configuration software tool with "office-like" interface and great ease of use, downloadable free of charge from the Notifier Italy website. Configuration of all control panel programming and transfer of programming with USB key without the need for cable connection to the control panel.
Features:
- Input: 100÷240Vac +/- 15%, 1.9A 50÷60Hz
- Voltage: 27.6Vdc - 7A total
- Battery Charging: 27.5Vdc 1.6A (with temperature compensation). Recommended batteries: 2 x 24 Ah
- Utility Output: 28Vdc (+3% +/ -18%) 3.5A, to power external loads such as: sirens, electromagnets, etc.
- Available current for each Line: 750 mA
- Operating temperature: -5 °C to +40 °C
- Storage temperature: -10 °C to +50 °C
- Degree of protection: IP30
- Dimensions: 483mm x 398mm x 217mm
- Weight: 9 Kg
Data sheet
- Type:
- Control units
- Zone:
- 4