Far thermostatic control 1828 with built-in liquid sensor 1828


RFR 1828 8052190858475

Far 1828 thermostatic control, with built-in liquid sensor for FAR thermostat valves:


  • Temperature adjustment range: 7°C (position) to 28°C (position 5)
  • Possibility of locking to desired value
  • Limitation of control range
  • Quick coupling on the thermostat valve


Keymark certified - EN215 compliant in conjunction with valve bodies ART.1620 12 and ART.1640 12

Do you have questions about this product or did you not find what you were looking for? Ask us!

Far thermostatic control 1828 with built-in liquid sensor 1828

€15.92
€15.92

Far thermostatic control 1828 with built-in liquid sensor 1828

€15.92
Tax included

Far thermostatic control 1828 with built-in liquid sensor 1828

€15.92

Buy it within and receive it from Monday, 11 November
Two-year warranty
Easy return within 14 days

SPECIFICATION ITEMS:

  • Thermostatic control with built-in liquid sensor, equipped with numbered selector corresponding to an adjustment range of 7÷28°C, locking device and temperature and adjustment range limitation. Complies with EN 215 in conjunction with valve bodies art.1620 12 and art.1640 12.

Advantages:

  • Adjustment range from 7°C to 28°C
  • Antifreeze position
  • Possibility of locking to the desired value
  • Setting of control range
  • Quick engagement on the thermostat valve
  • Keymark certification
  • TELL certification

The FAR thermostatic control regulates, through an internal liquid sensor sensitive to temperature changes, the opening and closing of the valve on which it is installed, thus balancing the temperature inside the room to be heated.


Features:

  • Maximum differential pressure: 1 bar
  • Reference point: 3 = 20° C
  • Maximum room temperature: 50° C
  • Maximum operating temperature (thermostat valve): 95°C
  • Temperature setting range: 7-28° C
  • Antifreeze intervention: 7° C
  • Hysteresis: C= 0.3 K
  • Response time: Z= 21 min
  • Nominal flow rate: qmN= 190 kg/h
  • Influence of temperature: W= 0.85 K
  • Influence of differential pressure: D= 0.25 K
  • Authority: a=0.85
  • Nominal Pressure: 10 bar
  • Control accuracy: CA= 0.6 K

Data sheet

Type:
Thermostatic Radiator Valves